Using datalinks with modbus, Modbus datalinks out: a…d, Using datalinks with modbus -3 – Rockwell Automation 20-COMM-H RS485 HVAC Adapter FRN 2.xxx User Manual

Page 69

Advertising
background image

Using Datalinks with All Protocols

7-3

20-COMM-H RS-485 HVAC Adapter User Manual

Publication 20COMM-UM009D-EN-P

Using Datalinks with Modbus

This section presents information about using Datalinks with Modbus
networks. For information about using Datalinks for Metasys N2 networks
or Siemens P1 FLN networks, refer to the

Using Datalinks with Metasys N2

or

Using Datalinks with Siemens P1 FLN

sections in this chapter.

Modbus Datalinks Out: A…D

Table 7.A Modbus Datalinks Out - A1, A2

Modbus
Address

Data Direction

Parameter
Description

16-Bit Datalink

32-Bit Datalink

3x0012

Register Input

Datalink A1 Out

Not used

LSW of 32-bit

3x0013

(1)

(1)

A read access to address 3x0013 initiates a refresh of Datalink A1 value before reading.

Register Input

Datalink A1 Out

16-bit value

MSW of 32-bit

3x0014

Register Input

Datalink A2 Out

Not used

LSW of 32-bit

3x0015

(2)

(2)

A read access to address 3x0015 initiates a refresh of Datalink A2 value before reading.

Register Input

Datalink A2 Out

16-bit value

MSW of 32-bit

Table 7.B Modbus Datalinks Out - B1, B2

Modbus
Address

Data Direction

Parameter
Description

16-Bit Datalink

32-Bit Datalink

3x0016

Register Input

Datalink B1 Out

Not used

LSW of 32-bit

3x0017

(1)

(1)

A read access to address 3x0017 initiates a refresh of Datalink B1 value before reading.

Register Input

Datalink B1 Out

16-bit value

MSW of 32-bit

3x0018

Register Input

Datalink B2 Out

Not used

LSW of 32-bit

3x0019

(2)

(2)

A read access to address 3x0019 initiates a refresh of Datalink B2 value before reading.

Register Input

Datalink B2 Out

16-bit value

MSW of 32-bit

Table 7.C Modbus Datalinks Out - C1, C2

Modbus
Address

Data Direction

Parameter
Description

16-Bit Datalink

32-Bit Datalink

3x0020

Register Input

Datalink C1 Out

Not used

LSW of 32-bit

3x0021

(1)

(1)

A read access to address 3x0021 initiates a refresh of Datalink C1 value before reading.

Register Input

Datalink C1 Out

16-bit value

MSW of 32-bit

3x0022

Register Input

Datalink C2 Out

Not used

LSW of 32-bit

3x0023

(2)

(2)

A read access to address 3x0023 initiates a refresh of Datalink C2 value before reading.

Register Input

Datalink C2 Out

16-bit value

MSW of 32-bit

Table 7.D Modbus Datalinks Out - D1, D2

Modbus
Address

Data Direction

Parameter
Description

16-Bit Datalink

32-Bit Datalink

3x0024

Register Input

Datalink D1 Out

Not used

LSW of 32-bit

3x0025

(1)

(1)

A read access to address 3x0025 initiates a refresh of Datalink D1 value before reading.

Register Input

Datalink D1 Out

16-bit value

MSW of 32-bit

3x0026

Register Input

Datalink D2 Out

Not used

LSW of 32-bit

3x0027

(2)

(2)

A read access to address 3x0027 initiates a refresh of Datalink D2 value before reading.

Register Input

Datalink D2 Out

16-bit value

MSW of 32-bit

Advertising