Using Datalinks with All Protocols

20-COMM-H RS-485 HVAC Adapter User Manual

Publication 20COMM-UM009D-EN-P

Note that certain drives may utilize 32-bit datalinks. In this case, Datalinks
are not supported by the adapter. The adapter will support only 15-bit
Datalink values.

Siemens P1 FLN Datalinks Out: A…D

P1 FLN devices work only with 15-bit integer values; therefore, these
points only show 15-bit values. If an adapter is connected to a host using
32-bit Datalinks, the adapter will be prevented from using Datalinks. The
DPI host determines if 16- or 32-bit Datalink values are used.

Siemens P1 FLN Datalinks In: A…D

P1 FLN devices work only with 15-bit integer values; therefore, these
points only show 15-bit values. If an adapter is connected to a host using
32-bit Datalinks, the adapter will be prevented from using Datalinks. The
DPI host determines if 16- or 32-bit Datalink values are used.

!

ATTENTION: Risk of injury or equipment damage exists. On
P1 FLN networks, 16-bit values are truncated to 15-bit values.
Unpredictable operation may result from using non-16-bit drive
parameters with the configurable points. Recognize the data
range limitation of P1 FLN and understand the data value ranges
of each parameter to be accessed over the network. Refer to the
drive user manual for information about drive parameter sizes.

Table 7.M Siemens P1 FLN Datalinks Out: A…D

Point
Number

(1)

(1)

Point numbers that appear in braces { } may be unbundled at the field panel.

Point
Type

Descriptor

Factory
Default

Description

{44}

LAI

DLINK A1 OUT

0

Bit 0…14 of Datalink Out A1

{46}

LAI

DLINK A2 OUT

0

Bit 0…14 of Datalink Out A2

{48}

LAI

DLINK B1 OUT

0

Bit 0…14 of Datalink Out B1

{50}

LAI

DLNK B2 OUT

0

Bit 0…14 of Datalink Out B2

{52}

LAI

DLNK C1 OUT

0

Bit 0…14 of Datalink Out C1

{54}

LAI

DLNK C2 OUT

0

Bit 0…14 of Datalink Out C2

{56}

LAI

DLNK D1 OUT

0

Bit 0…14 of Datalink Out D1

{58}

LAI

DLNK D2 OUT

0

Bit 0…14 of Datalink Out D2

Table 7.N Siemens P1 FLN Datalinks In: A…D

Point
Number

(1)

(1)

Point numbers that appear in braces { } may be unbundled at the field panel.

Point
Type

Descriptor

Factory
Default

Description

{62}

LAO

DLNK A1 IN

0

Bits 0…14 of Datalink In A1

{64}

LAO

DLNK A2 IN

0

Bits 0…14 of Datalink In A2

{66}

LAO

DLNK B1 IN

0

Bits 0…14 of Datalink In B1

{68}

LAO

DLNK B2 IN

0

Bits 0…14 of Datalink In B2

{70}

LAO

DLNK C1 IN

0

Bits 0…14 of Datalink In C1

{72}

LAO

DLNK C2 IN

0

Bits 0…14 of Datalink In C2

{74}

LAO

DLNK D1 IN

0

Bits 0…14 of Datalink In D1

{76}

LAO

DLNK D2 IN

0

Bits 0…14 of Datalink In D2