Viewing the logic status and feedback – Rockwell Automation 20-COMM-H RS485 HVAC Adapter FRN 2.xxx User Manual

Page 39

Advertising
background image

Using Modbus RTU

4-7

20-COMM-H RS-485 HVAC Adapter User Manual

Publication 20COMM-UM009D-EN-P

Table 4.F

shows the register outputs. These outputs must be used for writing

multi-bit commands and the Reference.

Viewing the Logic Status and Feedback

On Modbus RTU, there are two ways to view the logic status: discrete
inputs (

Table 4.G

) and register inputs (

Table 4.H on page 4-8

). You can use

discrete inputs when you need to view only one bit in the logic status word.
For example, to view whether a PowerFlex 70/700 drive is Ready (bit 0),
you can use a discrete input (Modbus Address 1x0001).

When you need to view multi-bit fields in the logic status word or to view
the entire logic status word, you must use a register input to maintain data
integrity. For example, to view the local control of a PowerFlex 70/700
drive (bits 9…11), you must use a register input (Modbus Address 3x0001).

To view the Feedback, you must also use a register input (Modbus Address
3x0002 and/or 3x0003). For details about how the feedback is scaled, refer
to the

Setting the Logic Command and Reference on page 4-5

.

Table 4.G

shows that there are 16 discrete points to represent the status

word bit by bit. These points can be used only for reading single-bit status.

Table 4.F Logic Command and Reference: Register Outputs

Modbus
Address

Output Description

Values

4x0001

Product Logic Command

16-bit word. Bit definitions for PowerFlex 70/700 drives are in

Table 4.E

. For other products, refer to their documentation.

4x0002

Reference Lo

Bit 0…15 of 32-bit reference.

4x0003

(1)

(1)

The reference value is sent only when accessing address 4x0003. If a 32-bit reference is used, the 32-bit value
will be merged together by register 4x0002 and 4x0003 when accessing address 4x0003.

Reference Hi

Bit 16…31 of 32-bit reference or the whole 16-bit reference.

Table 4.G Logic Status: Discrete Inputs (to Controller from Drive)

Modbus
Address

Logic Status Bit

PowerFlex 70/700 Example
Description

Values

1x0001

0

Ready

0 = Not Ready
1 = Ready

1x0002

1

Active

0 = Not Running
1 = Running

1x0003

2

Command Direction

0 = Reverse
1 = Forward

1x0004

3

Actual Direction

0 = Reverse
1 = Forward

1x0005

4

Accel

0 = Not Accelerating
1 = Accelerating

1x0006

5

Decel

0 = Not Decelerating
1 = Decelerating

1x0007

6

Alarm

0 = No Alarm
1 = Alarm

1x0008

7

Fault

0 = No Fault
1 = Fault

1x0009

8

At Speed

0 = Not At Reference
1 = At Reference