Viewing the adapter status using parameters, Viewing the adapter status using parameters -9 – Rockwell Automation 20-COMM-H RS485 HVAC Adapter FRN 2.xxx User Manual

Page 31

Advertising
background image

Configuring the Adapter

3-9

20-COMM-H RS-485 HVAC Adapter User Manual

Publication 20COMM-UM009D-EN-P

Viewing the Adapter Status
Using Parameters

The following parameters provide information about the status of the
adapter. You can view these parameters at any time.

Parameter

Description

04 - [Net Add Act]

Displays the actual network address of the adapter.

06 - [Net Rate Act]

Displays the network data rate actually used by the adapter. Only valid
values for the specified network are displayed.

08 - [Net Parity Act]

Displays the actual network parity used by the adapter. Only valid values
for the specified network are displayed.

09 - [Stop Bits Act]

Displays the actual number of stop bits used by the selected protocol.

This value is network-dependent:

ModBus RTU Protocol – The number of stop bits used depends on the
value set by Parameter 30 - [Stop Bits Cfg]). If the value is “0,” the
adapter uses 1 stop bit; otherwise, it uses 2 stop bits.

Metasys N2 Protocol – Uses only 1 bit, so the adapter shows only this
value.

Siemens Building Technologies P1 FLN Protocol – Uses only 1 bit, so
the adapter shows only this value.

10 - [Net Chksum Type] Displays the type of checksum used by the selected protocol. The values

are as follows:

CRC16 (0) is Cyclic Redundancy Check with 0 as a seed value. The
Siemens Building Technologies P1 FLN protocol uses this checksum.

RLC is Run Length Checksum. The Metasys N2 protocol uses this
checksum.

CRC16 (-1) is Cyclic Redundancy Check with -1 as a seed value. The
Modbus RTU protocol uses this checksum.

17 - [DPI I/O Act]

Displays the Reference/Feedback and Datalinks used by the adapter. This
value is the same as Parameter 16 - [DPI I/O Cfg] unless the parameter
was changed and the adapter was not reset.

Bit
Definition

Not Used

Not Used

Not Used

Datal

ink D

Datal

ink C

Datal

ink B

Datal

ink A

Cmd/Ref

Default

x

x

x 0 0 0 0 1

Bit

7 6 5 4 3 2 1 0

0 = I/O disabled
1 = I/O enabled