3-4

Configuring the Adapter

20-COMM-H RS-485 HVAC Adapter User Manual

Publication 20COMM-UM009D-EN-P

Setting the Network Parity

The parity that the adapter uses to verify data integrity varies based on the
type of network and your network configuration. Refer to the following
table.

1. Set the value of Parameter 07 - [Net Parity Cfg] to the type of parity

that is used on the network.

Figure 3.3

Example Network Parity Screen

2. Reset the adapter (see

Resetting the Adapter on page 3-8

). The actual

network parity is then displayed by Parameter 08 - [Net Parity Act].

Setting Stop Bits (Modbus
RTU only)

Parameter 30 - [Stop Bits Cfg] enables you to set 1 or 2 stop bits for the
Modbus RTU network protocol. When the adapter rotary switch is set to
“N2” or “P1,” the Stop Bits Cfg value is ignored and does not transfer to
read-only Parameter 09 - [Stop Bits Act] on power-up or reset (N2 and P1 are
fixed at 1 stop bit).

1. Set the value of Parameter 30 - [Stop Bits Cfg].

Figure 3.4

Example Stop Bits Screen

2. Reset the adapter (see

Resetting the Adapter on page 3-8

). The actual

stop bits is then displayed by Parameter 09 - [Stop Bits Act].

Network

Possible Types of Parity

Modbus RTU

None, Even, or Odd

Metasys N2

None

Siemens Building Technologies P1 FLN

None

Value

Type of Parity

0

None (default)

1

Odd

2

Even

Port 5 Device

20-COMM-H

Parameter #: 07
Net Parity Cfg

0

None

Value

Type of Stop Bit

0

1-bit (default)

1

2-bits

Port 5 Device

20-COMM-H

Parameter #: 30
Stop Bits Cfg

0

1-bit