Using Siemens Building Technologies P1 FLN

20-COMM-H RS-485 HVAC Adapter User Manual

Publication 20COMM-UM009D-EN-P

engineering value. For example, in PowerFlex 70/700 drives, the Reference
is scaled based on the value of Parameter 55 - [Maximum Freq], but the
commanded maximum speed can never exceed the value of Parameter 82 -
[Maximum Speed]
.

Table 6.C

shows example References and their results

on a PowerFlex 70/700 drive that has its Parameters 55 - [Maximum
Freq]
set to 130 Hz and 82 - [Maximum Speed] set to 60 Hz.

Table 6.D

shows the commands that you can execute on a PowerFlex 70/

700 drive and the point(s) that you can use to execute them.

Table 6.C Example Speed Reference and Feedback for a PowerFlex 70/700

Reference
Value

Scale

Output Speed

Feedback
Value

Percent

Value

32767

100%

130 Hz

60 Hz

(1)

(1)

The drive runs at 60 Hz instead of 130 Hz because Parameter 82 - [Maximum Speed]
sets 60 Hz as the maximum speed.

15123

(2)

(2)

The Feedback value is also scaled based on the value of Parameter 55 - [Maximum
Freq]. For example, 60/130 = 0.46 so 32767 x 0.46 = 15123.

16384

50%

65 Hz

60 Hz

(1)

15123

8192

25%

32.5 Hz

32.5 Hz

8192

0

0%

0 Hz

0 Hz

0

Table 6.D Logic Commands

Point
Number(s) Point

Logic
Command Bit

PowerFlex 70/700 Example
Descriptio
n

Values

24

CMD RUN.STOP

0

Stop

(1)

0 = Not Stop
1 = Stop

(3)

26

RUN ENABLE

89

LOGIC CMD LO bit 0

24

CMD RUN.STOP

1

Start

(1)

(2)

0 = Not Start
1 = Start

89

LOGIC CMD LO bit 0

89

LOGIC CMD LO bit 2 2

Jog

0 = Not Jog
1 = Jog

94

RESET FAULTS

3

Clear
Faults

(2)

0 = Not Clear Faults
1 = Clear Faults

89

LOGIC CMD LO bit 3

22

CMD FWD.REV

4 and 5

Direction

Bits

89

LOGIC CMD LO
bits 4, 5

05 04
0

0

= No Command

0

1

= Forward Command

1

0

= Reverse Command

1

1

= Hold Direction Control

89

LOGIC CMD LO bit 6 6

Local
Control

0 = No Local Control
1 = Local Control

89

LOGIC CMD LO bit 7 7

MOP
Increment

0 = Not Increment
1 = Increment

90

LOGIC CMD HI
bits 0, 1

8 and 9

Accel Rate

LOGIC CMD HI Bits
01 00
0

0

= No Command

0

1

= Accel Rate 1

1

0

= Accel Rate 2

1

1

= Hold Accel Rate

90

LOGIC CMD HI
bits 3, 2

10 and 11

Decel Rate LOGIC CMD HI Bits

03 02
0

0

= No Command

0

1

= Decel Rate 1

1

0

= Decel Rate 2

1

1

= Hold Decel Rate