Powerflex 700s drives, Logic command word (phase ii control) – Rockwell Automation 20-COMM-H RS485 HVAC Adapter FRN 2.xxx User Manual
Page 89

Logic Command/Status Words
C-3
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
PowerFlex 700S Drives
Logic Command Word (Phase II Control)
Logic Bits
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Command
Description
x
Normal Stop
0 = Not Normal Stop
1 = Normal Stop
x
Start
(1)
0 = Not Start
1 = Start
x
Jog 1
0 = Not Jog using [Jog Speed 1]
1 = Jog using [Jog Speed 1]
x
Clear Fault
(2)
0 = Not Clear Fault
1 = Clear Fault
x
x
Unipolar
Direction
00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Hold Direction Control
x
Reserved
x
Jog 2
0 = Not Jog using [Jog Speed 2]
1 = Jog using [Jog Speed 2]
x
Current Limit
Stop
0 = Not Current Limit Stop
1 = Current Limit Stop
x
Coast Stop
0 = Not Coast to Stop
1 = Coast to Stop
x
Reserved
x
Reserved
x
Spd Ref Sel0
x
Spd Ref Sel1
x
Spd Ref Sel2
x
Reserved
(1)
A Not Stop condition (logic bit 0 = 0, logic bit 8 = 0, and logic bit 9 = 0) must first be present before a 1 = Start condition will start the drive.
(2)
To perform this command, the value must switch from “0” to “1.”
Bits
14 13 12
0
0
0 = Spd Ref A
0
0
1 = Spd Ref B
0
1
0 = Preset 2
0
1
1 = Ref. 3 (Preset 3)
1
0
0 = Ref. 4 (Preset 4)
1
0
1 = Ref. 5 (Preset 5)
1
1
0 = Ref. 6 (Preset 6)
1
1
1 = Ref. 7 (Preset 7)