The P1 FLN point map provides points to monitor a number of other
features in the drive. These points include CURRENT (point 06), TORQUE
(point 07), and POWER (point 08). Refer to

Table 6.E

for a description of

the various points.

Using the P1 FLN Point Map to
Access Parameters

Drive parameters can be accessed using Configurable Points or Datalinks
(

Chapter 7

,

Using Datalinks with All Protocols

).

Reading Parameter Values

Configurable points USER IN (point 37) and PARAM IN (point 36) are
points that enable any parameter in the drive to be monitored. The USER IN
shows only 15-bit values; therefore, only 16-bit drive parameters can be
used (however, only values between 0…32767 would be used).

The PARAM IN is used to configure which parameter is to be monitored,
and the value ends up in the USER IN. For example, for a PowerFlex 70 or
700 drive, writing the value of “1” into PARAM IN point (reading drive
parameter 1) would provide the Output Frequency in USER IN point.

96

LOGIC STS HI
bits 7, 6, 5, 4

12, 13, 14,
and 15

Reference

LOGIC STS HI Bits
07 06 05 04
0

0

0

0

= Ref A Auto

0

0

0

1

= Ref B Auto

0

0

1

0

= Preset 2 Auto

0

0

1

1

= Preset 3 Auto

0

1

0

0

= Preset 4 Auto

0

1

0

1

= Preset 5 Auto

0

1

1

0

= Preset 6 Auto

0

1

1

1

= Preset 7 Auto

1

0

0

0

= Term Blk Manual

1

0

0

1

= DPI 1 Manual

1

0

1

0

= DPI 2 Manual

1

0

1

1

= DPI 3 Manual

1

1

0

0

= DPI 4 Manual

1

1

0

1

= DPI 5 Manual

1

1

1

0

= DPI 6 Manual

1

1

1

1

= Jog Ref

(1)

The values in this column are for LOGIC STS LO (point 95) and LOGIC STS HI (point 96). For details about
other point values, refer to

Table 6.B on page 6-3

.

Table 6.E Logic Status (Continued)

Point
Number(s) Point Name

Logic
Status Bit

PowerFlex 70/700 Example
Descriptio
n

Values

(1)

Advertising