Using Modbus RTU

20-COMM-H RS-485 HVAC Adapter User Manual

Publication 20COMM-UM009D-EN-P

Using the Modbus RTU Point
Map for I/O

On Modbus, data transfers are used to transfer the I/O data that controls the
drive and sets its Reference. Note that output I/O is data that the master
device sends and the adapter receives. Input I/O is status data that the
adapter sends and the master device receives.

Important: In order for the drive to use the I/O and Reference from the

Modbus RTU network, you must set parameters in it and the
adapter to receive the I/O and Reference. For details, refer to

Setting the I/O Configuration on page 3-5

.

Write Various Holding Registers

4x0001

Product Logic Command

4x0002

Reference Lo (Bits 0…15 of 32-bit Reference)

4x0003

Reference Hi (Bits 16…31 of 32-bit Reference or whole 16-bit Reference)

4x0004

Parameter # for USER IN1

4x0005

Parameter # for USER IN2

4x0006

Parameter # for USER IN3

4x0007

Parameter # for USER IN4

4x0008

Parameter # for USER IN5

4x0009

Parameter # for USER IN6

4x0010

Parameter # for USER IN7

4x0011

Parameter # for USER IN8

4x0012

Write USER OUT1

4x0013

Write USER OUT2

4x0014

Write USER OUT3

4x0015

Parameter # for USER OUT1

4x0016

Parameter # for USER OUT2

4x0017

Parameter # for USER OUT3

4x0018

Write Datalink A1 In

4x0019
4x0020

Write Datalink A2 In

4x0021
4x0022

Write Datalink B1 In

4x0023
4x0024

Write Datalink B2 In

4x0025
4x0026

Write Datalink C1 In

4x0027
4x0028

Write Datalink C2 In

4x0029
4x0030

Write Datalink D1 In

4x0031
4x0032

Write Datalink D2 In

4x0033

Direct Parameter Access

4x0100 + param #

20-COMM-H Parameter Direct Access (with adapter in 16-bit mode)

4x0100 + (param # x 2)

20-COMM-H Parameter Direct Access (with adapter in 32-bit mode)

4x1000 + param #

Drive Parameter Direct Access (with adapter in 16-bit mode)

4x1000 + (param # x 2)

Drive Parameter Direct Access (with adapter in 32-bit mode)

Table 4.C Adapter Modbus Register Map (Continued)

Modbus Register

Function