Quick Start 2-2

Publication 855T-UM001C-EN-P May 2005

Node Address Configuration

Rotary switches 1 (S1) and 2 (S2) set the node address (0…63) of the stack light on the
DeviceNet Network. The factory default is 63.

Figure 2.2

For more information on node address configuration, refer to Chapter 3 — Installation and
Mounting (Setting the DeviceNet Node Address).

Installing the Modules

The stack light modules are installed to the base by placing a sealing o-ring between the base
and the module, lining up the arrow on the bottom of the module with the line on the top of
the prior module or base, and twisting the top module clockwise to lock them into place.

For more information on different modules, refer to the Signal Solutions Selection Guide
(Publication 855-SG001*-EN-P) or the Industrial Controls Catalog.

Connection to the Network

Wire the DeviceNet Stack Light to an operating network. If the device is an 855T-DSxxxx,
the wires should be connected to a terminal block. If the device is an 855T-DMxxxx or
855T-DLxxxx, it will be connected with the quick disconnect connector. The device is fully
powered by the network, therefore it is important that the device is located near a power
supply.
For more information on system installation, refer to the DeviceNet Media Design Installation
Guide
(Publication DNET-UM072*-EN-P).

IMPORTANT

The DeviceNet Base is compatible with all 24V DC 855T modules.

DATA
RATE

PGM
500K

250K

NOT
USED

MSD

NODE ADDRESS

(00 – 63, PGM)

4

6

2

0

8

125K

PGM

0

LSD

2

4

6