DeviceNet Information B-12

Publication 855T-UM001C-EN-P May 2005

Instance 6 and 7 are the Group 3 Explicit Message Connections. The following instance 6
and 7 attributes will be supported:

The following common services will be implemented for the Connection Object.

Table B.17

Attribute
ID

Access
Rule

Name

Data Type

Value

1

Get

State

USINT

0 = nonexistent
1 = configuring
3 = established
4 = timed out

2

Get

Instance Type

USINT

0 = Explicit Message

3

Get

Transport Class Trigger

USINT

0x83 — Server,
Transport Class 3

4

Get

Produced Connection ID

UINT

11???xxxxxx

xxxxxx = node address

5

Get

Consumed Connection ID

UINT

11???xxxxxx

xxxxxx = node address

6

Get

Initial Comm. Characteristics

USINT

0x22

7

Get

Produced Connection Size

UINT

0x61

8

Get

Consumed Connection Size

UINT

0x61

9

Get/Set

Expected Packet Rate

UINT

In milliseconds

12 (0C

hex

)

Get

Watchdog Action

USINT

01 = auto delete
03 = deferred delete

13 (0D

hex

)

Get

Produced Connection Path
Length

UINT

0

14 (0E

hex

)

Get

Produced Connection Path

Empty

15 (0F

hex

)

Get

Consumed Connection Path
Length

UINT

0

16 (10

hex

)

Get

Consumed Connection Path

Empty

Table B.18

Service Code

Implemented for:

Service Name

Class

Instance

0x05

No

Yes

Reset

0x09

Yes

Yes

Delete

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single