Resetting the device, Devicenet operations, Error mode – Rockwell Automation 855T DeviceNet Stack Light User Manual User Manual

Page 38

Advertising
background image

4-8 Operations

Publication 855T-UM001C-EN-P May 2005

Error Mode

Errors are critical and non-critical.

Refer to the troubleshooting chart in Chapter 5 for details on how to recover from an error.

Resetting the Device

To reset the 855T Control Tower Stack Light, you must cycle power to the unit or disconnect
the DeviceNet Cabling

.

DeviceNet Operations

The Allen-Bradley 1747-SDN, 1771-SDN, and 1756-DNB DeviceNet Scanner Modules are
master devices on the DeviceNet Network. The 855T Control Tower Stack Light supports
the Master/Slave Connection Set for master/slave communications on the DeviceNet
Network.
To communicate with 855T Control Tower Stack Light, the DeviceNet Scanner Module must
be configured with the stack light:

• Node Address
• Input bytes (1)
• Output bytes (1)

The DeviceNet Scanner Module:

• connects to the 855T Control Tower Stack Light slave device.
• performs appropriate connection configuration.
• polls the 855T Control Tower Stack Light for I/O.

Table 4.P

Error Type

Description

Critical (non-recoverable)

• Failure of diagnostic tests during power-up/reset mode

• Duplicate node address detected

• Incorrect data rate

Non-Critical (recoverable)

• Pilot lamp burned out/module missing (power must be cycled to reset Status

Byte once lamp is changed)

• I/O connection timeout