background image

4-4 Operations

Publication 855T-UM001C-EN-P May 2005

Parameters 7, 9, 11, 13, 15 — Module Type

In normal operation the device will permit configuration of each module type. The default
type is 8, Invalid Module.

IMPORTANT

Although it is allowed, it is not recommended that strobe, sound, or
flashing modules be used with modes that flash.

Table 4.G Module Type

Type

Module

Type

Module

0

Incandescent

5

Combination Strobe/Sound

1

LED

6

Single Tone Sound

2

Strobe

7

Dual Tone Sound

3

Combination Incandescent/Sound

8

Invalid Module

4

Combination LED/Sound

IMPORTANT

The module type list is abbreviated. If the module is a rotating, flashing,
or steady LED, then select the LED as the module type. If the module
type is a flashing incandescent, then select Incandescent as the module
type. The same logic applies to combination light/sound type modules.