DeviceNet Information B-8

Publication 855T-UM001C-EN-P May 2005

Class Code 0x0005: Connection Object

No class attributes will be supported for the Connection Object.
Three instances of the Connection Object will be supported. Instance 1 will be the explicit
message connection, instance 2 will be the polled IO connection, and instance 4 will be the
COS/Cyclic IO connection.
Instance 1 is the Predefined Group 2 Connection Set Explicit Message Connection. The
following instance 1 attributes will be supported:

Table B.13

Attribute
ID

Access
Rule

Name

Data Type

Value

1

Get

State

USINT

0 = nonexistent
1 = configuring
3 = established
4 = timed out

2

Get

Instance Type

USINT

0 = Explicit Message

3

Get

Transport Class Trigger

BYTE

0x83 — Server,
Transport Class 3

4

Get

Produced Connection ID

UINT

10xxxxxx011

xxxxxx = node address

5

Get

Consumed Connection ID

UINT

10xxxxxx100

xxxxxx = node address

6

Get

Initial Comm. Characteristics

BYTE

0x22

7

Get

Produced Connection Size

UINT

0x61

8

Get

Consumed Connection Size

UINT

0x61

9

Get/Set

Expected Packet Rate

UINT

In milliseconds

12 (0C

hex

)

Get

Watchdog Action

USINT

01 = auto delete
03 = deferred delete

13 (0D

hex

)

Get

Produced Connection Path
Length

UINT

0

14 (0E

hex

)

Get

Produced Connection Path

EPATH

Empty

15 (0F

hex

)

Get

Consumed Connection Path
Length

UINT

0

16 (10

hex

)

Get

Consumed Connection Path

EPATH

Empty