Rockwell Automation 855T DeviceNet Stack Light User Manual User Manual
Page 59

DeviceNet Information B-10
Publication 855T-UM001C-EN-P May 2005
Instance 4 is the Predefined Group 2 Connection Set Change of State/Cyclic I/O Message
Connection. The following instance 4 attributes will be supported:
Table B.15
Attribute
ID
Access
Rule
Name
Data Type
Value
1
Get
State
USINT
0 = nonexistent
1 = configuring
3 = established
4 = timed out
2
Get
Instance Type
USINT
1 = I/O Connection
3
Get
Transport Class Trigger
USINT
0x00 (Cyclic,
unacknowledged)
0x03 (Cyclic,
acknowledged)
0x10 (COS,
unacknowledged)
0x13 (COS,
acknowledged)
4
Get
Produced Connection ID
UINT
01101xxxxxx
xxxxxx = node address
5
Get
Consumed Connection ID
UINT
10xxxxxx101
xxxxxx = node address
6
Get
Initial Comm. Characteristics
USINT
0x01 (acknowledged)
0x0F (unacknowledged)
7
Get
Produced Connection Size
UINT
0…8
8
Get
Consumed Connection Size
UINT
0…8
9
Get/Set
Expected Packet Rate
UINT
In milliseconds
12 (0C
hex
)
Get
Watchdog Action
USINT
0 = transition to timed
out
1 = auto delete
2 = auto reset
13 (0D
hex
)
Get
Produced Connection Path
Length
UINT
6
14 (0E
hex
)
Get
Produced Connection Path
—
20 04 24
(assy inst #) 30 03
15 (0F
hex
)
Get
Consumed Connection Path
Length
UINT
4 (acknowledged)
0 (unacknowledged)
16 (10
hex
)
Get/Set
Consumed Connection Path
—
20 04 24
(assy inst #) 30 03
17 (11
hex
)
Get/Set
Production Inhibit Time
UINT
In milliseconds