Rockwell Automation 855T DeviceNet Stack Light User Manual User Manual

Page 59

Advertising
background image

DeviceNet Information B-10

Publication 855T-UM001C-EN-P May 2005

Instance 4 is the Predefined Group 2 Connection Set Change of State/Cyclic I/O Message
Connection. The following instance 4 attributes will be supported:

Table B.15

Attribute
ID

Access
Rule

Name

Data Type

Value

1

Get

State

USINT

0 = nonexistent
1 = configuring
3 = established
4 = timed out

2

Get

Instance Type

USINT

1 = I/O Connection

3

Get

Transport Class Trigger

USINT

0x00 (Cyclic,
unacknowledged)
0x03 (Cyclic,
acknowledged)
0x10 (COS,
unacknowledged)
0x13 (COS,
acknowledged)

4

Get

Produced Connection ID

UINT

01101xxxxxx
xxxxxx = node address

5

Get

Consumed Connection ID

UINT

10xxxxxx101

xxxxxx = node address

6

Get

Initial Comm. Characteristics

USINT

0x01 (acknowledged)
0x0F (unacknowledged)

7

Get

Produced Connection Size

UINT

0…8

8

Get

Consumed Connection Size

UINT

0…8

9

Get/Set

Expected Packet Rate

UINT

In milliseconds

12 (0C

hex

)

Get

Watchdog Action

USINT

0 = transition to timed
out
1 = auto delete
2 = auto reset

13 (0D

hex

)

Get

Produced Connection Path
Length

UINT

6

14 (0E

hex

)

Get

Produced Connection Path

20 04 24
(assy inst #) 30 03

15 (0F

hex

)

Get

Consumed Connection Path
Length

UINT

4 (acknowledged)

0 (unacknowledged)

16 (10

hex

)

Get/Set

Consumed Connection Path

20 04 24
(assy inst #) 30 03

17 (11

hex

)

Get/Set

Production Inhibit Time

UINT

In milliseconds