Operations 4-5

Publication 855T-UM001C-EN-P May 2005

Parameters 8, 10, 12, 14, 16 — Module Mode

Parameter 17 — Set to Defaults

This parameter can be used to return the Bulletin 855T stack light to the “out of the box”
settings. This is the easiest way to clear an unwanted configuration. The default is No Action.

Table 4.H Operating Modes

Mode

Function

0

Self Test

1

For Future Use

2

For Future Use

3

Follows Module status LED

4

Follows Network status LED

5

Manual Operation, controlled by network (PLC/PC)

6

For Future Use

7

For Future Use

8

IEC Fast Rate flash: 2 Hz, 50% duty cycle

9

For Future Use

10

For Future Use

11

IEC Slow Rate flash: 0.6 Hz, 50% duty cycle

12

For Future Use

13

For Future Use

14

Horn cycle: 30 s ON/10 s OFF

15

WALK: Sequence with other Mode 15 lights as: 1;2;3;4;5;1;2;…

16

STACK: Sequence with other Mode 16 lights as: 1;1&2;1&2&3;…;1&2&3&4&5;1

17

Binary count displayed on available Lamps

18

Odd/Even IEC Fast Rate Flash — All even number lights flash opposite all odd number lights.

19…255

Reserved

Table 4.I

Value

Function

Value

Function

0

No Action

1

Reset