3-3 Installation and Mounting

Publication 855T-UM001C-EN-P May 2005

The data rate determines the maximum length of the DeviceNet Cable.

To set the DeviceNet data rate:

1. Refer to the table above to select the correct data rate.

2. If automatic baud rate selection is desired, set switch 3 (S3) in position 3. This

disables the switch and allows the device to sync to an operational network (if
Autobaud is disabled through parameter setup, this position is not valid).

Setting the DeviceNet Node Address

Rotary switches 1 (S1) and 2 (S2) set the node address (0…63) of the stack light on the
DeviceNet Network. The factory default is 63.

Figure 3.3

To set the DeviceNet node address:

1. Set Most Significant Digit (MSD) Switch, switch 2 (S2), to tens position. For example,

if the desired node address is 27, set switch 2 (S2) to 2.

2. Set Least Significant Digit (LSD) Switch, switch 1 (S1), to ones position. For example,

if the desired node address is 27, set switch 1 (S1) to 7.

3. If software programmability is desired, set the node address to 64 or greater. This

disables both switches and allows programming through the network. Software will
default to 63.

Table 3.B

Position

Data Rate

Cable Length (Max.)

0

125 KB

500 m (1600 ft)

1

250 KB

200 m (600 ft)

2

500 KB

100 m (300 ft)

3

Autobaud

See above, based on data rate of connected network

DATA
RATE

PGM
500K

250K

NOT
USED

MSD

NODE ADDRESS

(00 – 63, PGM)

4

6

2

0

8

125K

PGM

0

LSD

2

4

6