Rockwell Automation 1756-L7x GuardLogix 5570 Controllers User Manual

Page 114

Advertising
background image

114

Rockwell Automation Publication 1756-UM022A-EN-P - November 2012

Chapter 8

Store and Load Projects Using Nonvolatile Memory

Firmware Supervisor supports non-modular distributed I/O products that sit
directly on the network without an adapter, including CIP Safety I/O modules
on EtherNet/IP networks. CIP Safety I/O modules on DeviceNet networks and
POINT Guard I/O modules are not yet supported.

Follow these steps to enable Firmware Supervisor.

1. On the Controller Properties dialog box, click the Nonvolatile Memory

tab.

2. Click Load/Store.

3. From the Automatic Firmware Updates pull-down menu, choose Enable

and Store Files to Image.

The Logix Designer application moves the firmware kits from your computer to
the controller memory card for Firmware Supervisor to use.

TIP

If you disable Firmware Supervisor, you disable only firmware supervisor
updates. This does not include the controller firmware updates that occur
when the controller image is reloaded from the memory card.