Replacement with ‘configure only when – Rockwell Automation 1756-L7x GuardLogix 5570 Controllers User Manual

Page 70

Advertising
background image

70

Rockwell Automation Publication 1756-UM022A-EN-P - November 2012

Chapter 5

Add, Configure, Monitor, and Replace CIP Safety I/O

If the entire routable CIP Safety control system is not being relied on to maintain
SIL 3/PLe during the replacement and functional testing of a module, the
Configure Always feature may be used. Go to

Replacement with ‘Configure

Always’ Enabled on page 74

.

Module replacement is configured on the Safety tab of the GuardLogix
controller.

Figure 21 - Safety I/O Module Replacement

Replacement with ‘Configure Only When No Safety Signature Exists’
Enabled

When a module is replaced, the configuration will be downloaded from the
safety controller if the DeviceID of the new module matches the original. The
DeviceID is a combination of the node/IP address and the Safety Network
Number (SNN) and is updated whenever the SNN is set.

If the project is configured as ‘Configure Only When No Safety Signature Exists’,
follow the appropriate steps in

Table 23

to replace a POINT Guard I/O module

based on your scenario. Once you have completed the steps correctly, the
DeviceID will match the original, enabling the safety controller to download the
proper module configuration, and re-establish the safety connection.

Table 23 - Replacing a Module

GuardLogix Safety
Signature Exists

Replacement
Module Condition

Action Required

No

No SNN
(Out-of-box)

None. The module is ready for use.

Yes or No

Same SNN as original
safety task
configuration

None. The module is ready for use.