Rockwell Automation Publication 1756-UM022A-EN-P - November 2012

87

Develop Safety Applications

Chapter 6

To properly configure produced and consumed safety tags to share data between
peer safety controllers, you must properly configure the peer safety controllers,
produce a safety tag, and consume a safety tag, as described below.

Configure the Peer Safety Controllers’ Safety Network Numbers

The peer safety controller is subject to the same configuration requirements as
the local safety controller. The peer safety controller must also have a safety
network number (SNN). The SNN of the peer safety controller depends upon
its placement in the system.

Follow these steps to copy and paste the SNN.

1. Add the producer controller to the consumer controller’s I/O tree.

2. In the producer controller’s project, right-click the producer controller and

choose Controller Properties.

Table 29 - SNN and Controller Placement

Peer Safety Controller Location

SNN

Placed in the local chassis

GuardLogix controllers located in a common chassis
should have the same SNN.

Placed in another chassis

The controller must have a unique SNN.

Consumer Controller

Producer Controller