The safety partner has an OK status indicator.

Controller Status Display

The controller status display scrolls messages that provide information about the
controller’s firmware revision, energy storage module (ESM) status, project
status, and major faults.

Safety Status Messages

The primary controller display may show the following messages. The safety
partner displays ‘L7SP’.

General Status Messages

The messages described in

Table 46

are typically indicated upon powerup,

powerdown, and while the controller is running. These messages indicate the
status of the controller and the ESM.

Table 44 - 1756-L7SP Status Indicator

Indicator

Status

Description

OK

Off

No power is applied.

Green

The safety partner is operating with no faults.

Red

Powering up or nonrecoverable controller fault.

Table 45 - Safety Status Display

Message

Interpretation

No Safety Signature

Safety Task is in Run mode without a safety task signature.

Safety Partner Missing

The safety partner is missing or unavailable.

Hardware Incompatible

The safety partner and primary controller hardware is incompatible.

Firmware Incompatible

The safety partner and primary controller firmware revision levels are incompatible.

No CST Master

A coordinated system time (CST) master has not been found

Safety Task Inoperable

The safety logic is invalid. For example, a mismatch occurred between the primary
controller and the safety partner, a watchdog timeout occurred, or memory is corrupt.

Safety Unlocked

The controller is in Run mode with a safety signature, but is not safety-locked.

Table 46 - General Status Display

Message

Interpretation

No message is indicated

The controller is off, or a major nonrecoverable fault (MNRF) has occurred.
Check the OK indicator to determine if the controller is powered and determine the state of the controller.

TEST

Power-up tests are being conducted by the controller.

PASS

Power-up tests have been successfully completed.

SAVE

A project is being saved to the SD card at powerdown. You can also view the SD Indicator (see page

125

) for additional status information.

Allow the save to complete before removing the SD card or disconnecting power.