Status Indicators

Appendix A

LOAD

A project is being loaded from the SD card at controller powerup. You can also view the SD Indicator (see page

125

) for additional status information.

Allow the load to complete before removing the SD card, removing the ESM module, or disconnecting power.

UPDT

A firmware upgrade is being conducted from the SD card upon powerup. You can also view the SD Indicator (see page

125

) for additional status

information.
If you do not want the firmware to update upon powerup, change the controller’s Load Image property.

CHRG

The capacitor-based ESM is being charged.

1756-L7x/X

The controller catalog number and series.

Rev XX.xxx

The major and minor revision of the controller’s firmware.

No Project

No project is loaded on the controller.
To load a project, use the Logix Designer application to download the project to the controller, or use a SD card to load a project to the controller.

Project Name

The name of the project that is currently loaded on the controller. The name indicated is based on the project name specified in the Logix Designer
application.

BUSY

The I/O modules associated with the controller are not yet fully-powered.
Allow time for powerup and I/O module self-testing.

Corrupt Certificate
Received

The security certificate associated with the firmware is corrupted.
Go to

http://www.rockwellautomation.com/support/

and download the firmware revision you are trying to upgrade to. Replace the firmware revision you

have previously installed with that posted on the Technical Support website.

Corrupt Image Received

The firmware file is corrupted.
Go to

http://www.rockwellautomation.com/support/

and download the firmware revision you are trying to upgrade to. Replace the firmware revision you

have previously installed with that posted on the Technical Support website.

ESM Not Present

An ESM is not present and the controller cannot save the application at powerdown.
Insert a compatible ESM, and, if using a capacitor-based ESM, do not remove power until the ESM is charged.

ESM Incompatible

The ESM is incompatible with the memory size of the controller.
Replace the incompatible ESM with a compatible ESM.

ESM Hardware Failure

A failure with the ESM has occurred and the controller is incapable of saving of the program in the event of a powerdown.
Replace the ESM before removing power to the controller so the controller program is saved.

ESM Energy Low

The capacitor-based ESM does not have sufficient energy to enable the controller to save the program in the event of a powerdown.
Replace the ESM.

ESM Charging

The capacitor-based ESM is charging.
Do not remove power until charging is complete.

Flash in Progress

A firmware upgrade initiated via ControlFLASH or AutoFlash software is in progress.
Allow the firmware upgrade to complete without interruption.

Firmware Installation
Required

The controller is using boot firmware (that is revision 1.xxx) and requires a firmware upgrade.
Upgrade controller firmware.

SD Card Locked

An SD card that is locked is installed.

Table 46 - General Status Display