Chapter 5

Add, Configure, Monitor, and Replace CIP Safety I/O

Scenario 3 - Replacement Module SNN is Different from Original and No Safety Signature Exists

1. Remove the old I/O module and install the new module.

2. Right-click your POINT Guard I/O module and choose Properties.

3. Click the Safety tab.

4. Click Reset Ownership.

5. Click OK.

6. Follow your company-prescribed procedures to functionally test the

replaced I/O module and system and to authorize the system for use.

Replacement with ‘Configure Always’ Enabled

When the ‘Configure Always’ feature is enabled in the controller project, the
controller automatically checks for and connects to a replacement module that
meets all of the following requirements:

The controller has configuration data for a compatible module at that

network address.

The module is in out-of-box condition or has an SNN that matches the

configuration.

ATTENTION: Enable the Configure Always’ feature only if the entire CIP Safety
Control System is not being relied on to maintain SIL 3 behavior during the
replacement and functional testing of a module.

Do not place modules that are in the out-of-box condition on a CIP Safety network
when the Configure Always feature is enabled, except while following this
replacement procedure.