Rockwell Automation Publication 1756-UM022A-EN-P - November 2012

65

Add, Configure, Monitor, and Replace CIP Safety I/O

Chapter 5

Delay. This method can be used on an input or output connection. After the
system has been run for an extended period of time through its worst-case loading
conditions, record the Maximum Observed Network Delay.

The Network Delay Multiplier can be approximated by the following equation:

[Maximum Observed Network Delay + Margin_Factor]

÷

RPI

Understanding the
Configuration Signature

Each safety device has a unique configuration signature, which defines the
module configuration. The configuration signature is composed of an ID
number, date, and time, and is used to verify a module’s configuration.

Configuration via the Logix Designer Application

When the I/O module is configured by using the Logix Designer application, the
configuration signature is generated automatically. You can view and copy the
configuration signature via the Safety tab on the Module Properties dialog box.

Figure 20 - View and Copy the Configuration Signature

EXAMPLE

Calculate the Network Delay Multiplier from Maximum
Observed Network Delay

If:

RPI = 50 ms
Maximum Observed Network Delay = 20 ms
Margin_Factor = 10

Then, the Network Delay Multiplier equals:

[20 + 10]

÷

50 = 60%

Table 18 - Additional Resources

Resource

Description

GuardLogix 5570 Controllers Systems Safety Reference
Manual, publication

1756-RM099

Provides information on calculating reaction times.

Guard I/O DeviceNet Safety Modules User Manual, publication

1791DS-UM001

Guard I/O EtherNet/IP Safety Modules User Manual,
publication

1791ES-UM001