Status Indicators

Controllers Status Indicators

The status of the primary controller is displayed via four status indicators.

Topic

Page

Controllers Status Indicators

125

Controller Status Display

126

Table 43 - Primary Controller Status Indicator Descriptions

Indicator

Status

Description

RUN

Off

No user tasks running. Controller is in PROGram mode.

Green

Controller is in RUN mode.

FORCE

Off

No forces, standard or safety, are enabled on the controller.

Amber

Standard and/or safety forces have been enabled.
Use caution if you install (add) a force. If you install a force, it
takes immediate effect.

Amber, Flashing

One or more I/O addresses, standard and/or safety, have been forced to
an on or off state, but forces are not enabled.
Use caution if you enable I/O forces. If you enable I/O forces, all
existing I/O forces also take effect.

SD

Off

No activity is occurring with the memory card.

Green, Flashing

The controller is reading from or writing to the memory card. Do not
remove the memory card while the controller is reading or writing.

Green

Red, Flashing

The memory card does not have a valid file system.

Red

The memory card is not recognized by the controller.

OK

Off

No power is applied.

Green

The controller is operating with no faults.

Red, Flashing

Nonrecoverable fault or recoverable fault not handled in the fault

handler. All user tasks, both standard and safety, are stopped.

If the controller is new, out-of-the-box, it requires a firmware

upgrade. The status display indicates Firmware Installation
Required.

Red

The controller is completing power-up diagnostics
A nonrecoverable major fault occurred and the program was cleared

from memory.

The charge of the capacitor in the Energy Storage Module (ESM) is

being discharged upon powerdown.

The controller is powered but inoperable.
The controller is loading a project to nonvolatile memory.