Rockwell Automation 1756-L7x GuardLogix 5570 Controllers User Manual

Page 48

Advertising
background image

48

Rockwell Automation Publication 1756-UM022A-EN-P - November 2012

Chapter 4

Communicate over Networks

Copy and Paste a Safety Network Number (SNN)

If the module’s configuration is owned by another controller, you may need to
copy and paste the SNN from the configuration owner into the module in your
I/O configuration tree.

1. In the software configuration tool of the module’s configuration owner,

open the Safety Network Number dialog box for the module.

2. Click Copy.

3. Click the General tab on the Module Properties dialog box of the I/O

module in the I/O Configuration tree of the consuming controller project.
This consuming controller is not the configuration owner.

4. Click

to the right of the safety network number to open the Safety

Network Number dialog box.

5. Click Paste.

6. Click OK.