Rockwell Automation Publication 1756-UM022A-EN-P - November 2012

31

Install the Controller

Chapter 2

3. Click RSWho to specify the controller path.

4. Select your controller and click Update Firmware.

5. Select the firmware revision you want.

6. Click Update.

7. Click Yes.

Allow the firmware update to complete without interruption. When the
firmware upgrade is complete, the Who Active dialog box opens. You may
complete other tasks in the Logix Designer application.

Choose the Operating Mode
of the Controller

Use this table as a reference when determining your controller Operation mode.

Use the Keyswitch to Change the Operation Mode

The keyswitch on the front of the controller can be used to change the controller
to one of these modes:

Program (PROG)
Remote (REM)
Run (RUN)

Table 9 - Controller Operation Modes

If you want to

Select one of these modes

Run

Remote

Program

Run

Test

Program

Turn outputs to the state commanded by the logic of the
project

X

X

Turn outputs to their configured state for Program mode

X

X

X

Execute (scan) tasks

X

X

X

Change the mode of the controller through software

X

X

X

Download a project

X

X

X

X

Schedule a ControlNet network

X

X

While online, edit the project

X

X

X

X

Send messages

X

X

X

Send and receive data in response to a message from
another controller

X

X

X

X

X

Produce and consume tags

X

X

X

X

X