Constructing RS-232-C and

Longline Cables

Appendix A

A-11

Figure A.15

A longline connection from a 1771ĆKE, 1771ĆKF, or 1771ĆKG module to a

1773ĆKA or 1775ĆKA module.

2

14

3

13

4
5
6
8

11

1
3

25

2

4
5

1

6
8

20

7

15-pin Male

Connector

RS-232-C

PORT Connector

of 1771-KE,

1771-KF, or

1771-KG

Module

RS-232-C

PORT Connector

of 1773-KA

or 1775-KA

Module

25-pin Male

Connector

Connect the shield

at one end only

User-supplied cable,

Belden 8723, or Equivalent

(7000 ft. max)

NOTE: User supplied male connectors

12542

Important: For cables longer than 50 feet, conductors 2 and 14, and 3 and 13
must be twisted pairs.

Important: For a 1775-KA module, turn off (open) switch 3 on the module.