Go to step 15 – Rockwell Automation 1770 DH,DHII,DH485 CABLE User Manual

Page 37

Advertising
background image

Constructing a Data Highway or

Data Highway Plus Cable System

Chapter 3

3-5

11.

Connect the dropline to the 3-position terminal block connector.

Secure this wire:

To this terminal:

Clear conductor wire

1

Drain wire

SH

Blue conductor wire

2

Clear

Shield

Blue

Clear

Shield

Blue

1

SH

2

1

SH

2

Terminals on

3 -pin terminal block

Twinaxial cable

19603

Go to step 15.

12.

Connect the dropline to the 9-pin electrical connector.

Connect this wire:

To this pin number:

Blue conductor wire

5

Drain wire

7

Clear conductor wire

1

Blue

Drain

Clear

Twinaxial Cable

5

7

1

18767

Go to step 15.