Go to step 15 – Rockwell Automation 1770 DH,DHII,DH485 CABLE User Manual
Page 37
Advertising
Constructing a Data Highway or
Data Highway Plus Cable System
Chapter 3
3-5
11.
Connect the dropline to the 3-position terminal block connector.
Secure this wire:
To this terminal:
Clear conductor wire
1
Drain wire
SH
Blue conductor wire
2
Clear
Shield
Blue
Clear
Shield
Blue
1
SH
2
1
SH
2
Terminals on
3 -pin terminal block
Twinaxial cable
19603
Go to step 15.
12.
Connect the dropline to the 9-pin electrical connector.
Connect this wire:
To this pin number:
Blue conductor wire
5
Drain wire
7
Clear conductor wire
1
Blue
Drain
Clear
Twinaxial Cable
5
7
1
18767
Go to step 15.