Chapter 3

Constructing a Data Highway or

Data Highway Plus Cable System

3-32

If you choose, you may construct your DH+ network using a daisy chain
configuration, as shown below.

Node

Node

Node

Node

18768

To make daisy chain DH+ connections, connect the twinaxial cable to the
corresponding DH+ connector terminals on the terminal block of both devices
(Figure 3.10).

Figure 3.10

Terminal connections when nodes are daisy chained.

Clear

Drain

Blue

Clear

Drain

Blue

Twinaxial

cable

Terminating

Resistor

Clear

Drain

Blue

Clear

Drain

Blue

Twinaxial

cable

Terminating

Resistor

18769

After connecting all nodes to the DH+ network, you must install a 150 ohm 1/4
watt terminating resistor at each end of the network (Figure 3.10). Some DH+
modules provide an internal resistor option for this purpose. Refer to the manual
for the particular module you are using to see if this option is available.

Construct a Network Using a

Daisy Chain Configuration

(DH+ Only)