Constructing a Data Highway or

Data Highway Plus Cable System

Chapter 3

3-23

d.

Cut the blue conductor wire and the clear conductor wire to
approximately 0.35 inch (8.9 mm), as measured from the outside
surface of the insulating washer.

Cone Assembly

Insulating

Washer

18741

8.89mm

(0.35")

Conductor

Wires

e.

Using wire strippers, strip approximately 0.10 inch
(2.5 mm) of insulation off the end of the blue conductor wire.

f.

Using wire strippers, strip approximately 0.20 inch
(5.0 mm) of insulation off the end of the clear conductor wire.

5.0mm

(0.2")

Clear Conductor Wire

Blue Conductor Wire

2.5mm

(0.1")

Insulation

Insulating

Washer

Cone

Assembly

10807B

3.

Solder the connector wires.

a.

Bend the clear conductor wire so that it is at a right angle to the blue
conductor wire.

Clear

Conductor Wire

Blue

Conductor Wire

Cone

Assembly

18732