Constructing a Data Highway or
Data Highway Plus Cable System
Chapter 3
3-15
Mount the Station Connector
Now that all the necessary connections are made to the station connector, mount
the station connector by following these steps.
1.
Select a secure foundation for mounting the station connector. If necessary,
drill and/or tap mounting holes according to the dimensions shown in
Figure 3.4.
Figure 3.4
If necessary, drill and/or tap mounting holes for the station connector.
10.8cm
(4.25")
13.5cm
(W = 5.3")
8.1cm
(D = 3.2")m
5.1cm
(2.0")
10.2cm
(4.0")
14.0cm
(L = 5.5")
12.1cm
(4.75")
Terminal Block
Top View, Less Cover
Side View
11274
2.
If you removed the terminal block from the station connector, mount the
block inside the enclosure.
3.
Attach the ground wire from the station connector to earth ground. The lug
on the end of the ground wire accepts a number 10 screw.
Important: In the next step, do not pinch any wires between the cover plate and
the station connector enclosure. Also do not damage the gasket on the cover
plate, since this can nullify the NEMA type 13 rating of the station connector.
4.
Attach the cover plate to the station connector.