Planning a Data Highway or Data Highway Plus

Cable System

Chapter 2

2-5

The following sections describe the two types of station connectors in
more detail.

1770-SC Station Connector
The 1770-SC station connector can be used on either a DH or DH+
network and can be used instead of the 1770-XG connector kit (described
later in this chapter).

You need one 1770-SC station connector for each node you want to
connect to the network.

Each station connector connects one dropline to the trunkline and contains
the following components:

a junction box with a removable cover

a terminal block wired with the following:

- 0.05 mfd 500V DC capacitor (terminals 4 and 5)

- jumper (terminals 7 and 9)

- ground wire (terminal 10)

- earth ground wire with lug

a packet containing the following:

- D-shell cable connector hood

- 15-socket female connector

- packet of assembly hardware for the cable connector

- terminator resistor (150 ohm, 1/4 watt)

- shrink tubing

- cable clamp plug

installation

instructions

For information on installing a 1770-SC station connector, refer
to Chapter 3.