Constructing a DH II Cable System

Chapter 6

6-2

Mount the tap no more than 11 inches (28.0 cm) from the bottom or left side

of the interface module to make sure the dropline cable bend-radius is not
less than 3 inches (7.6 cm).

Do not mount the tap in a position that routes the dropline cable over the ac

power terminals on the interface module.

Do not allow the metal shell of the tap to touch a conductive surface.

If you are using a PLC-3 interface module (catalog numbers 1779-KP3 or

1779-KP3R) you must mount the tap no more than 5 inches (12.7 cm) from
the PLC-3 chassis. You can mount the tap on the side of the chassis only if
the interface module is at the end of the chassis.

Figure 6.1 shows the dimensions of a tap.

Figure 6.1

Dimensions of a tap.

25mm

(1.0 in)

38mm

(1.5 in)

54mm

(2.1 in)

79mm

(3.1 in)

89mm

(3.5 in)

6mm

(0.2 in)

Clearance Depth:

77mm (5 in)

Use No. 5

mounting bolts

2 places

12644