Constructing a Data Highway or

Data Highway Plus Cable System

Chapter 3

3-9

Electrical Short Exists and Dropline Has Station Connector
Disassemble the electrical connector and the station connector and try to locate
and correct the short. Check the resistances.

If the resistance readings:

Then:

Indicate there are no shorts

Attach the dropline to the trunkline. Refer to the appropriate

section later in this chapter.

Indicate that a short exists

The short is probably inside the dropline cable. Discard the

dropline cable and attach the electrical connector to a new piece

of cable. You may remove the connector from the discarded

dropline and reuse it on the new dropline.

Install the 1770ĆSC Station Connector

Use this section to construct a trunkline using a 1770-SC station connector.
These procedures apply to both DH and DH+ networks. Here is a brief outline
of the procedures you will follow when constructing a trunkline using the
1770-SC station connector.

connect the dropline to the station connector

connect the trunkline segments to the station connector

terminate the trunkline

mount the station connector

Important: If necessary, install the electrical connector to the dropline as
explained in the section, ‘‘Attach an Electrical Connector to the Dropline”
earlier in this chapter.

A 1770-SC station connector links a dropline cable to the trunkline and also
links two trunkline segments together.