Publication 2727-UM002D-EN-P

5-22 Using RSView ME Station

Advanced Settings for Diagnostic Messages and Alarm Messages

The following screen configures when to print diagnostic or alarm
messages that are sent to the Network or port.

To configure how messages are queued for printing, select the Print
Messages After
button and set one of the following options:

Specified number of messages

Prints messages after 60 are queued or another specified value.
The default is 60 (about one full page of messages.)

500 messages or timeout period, whichever is first

Prints after 500 messages are queued or a specific time period
has elapsed, whichever comes first. The default time period is
168 hours (7 days). You can specify another value. For example,
if 350 messages are in the queue and 7 days have elapsed, the
350 messages will print.

Specified number of messages or timeout period,

whichever is first

Prints after a specified number of messages are queued or a
specific time period has elapsed, whichever comes first.

The default number of messages to queue is 60. The default
timeout period is 168 hours (7 days). You can change both
values. For example, the number of messages is set to 75 and
the timeout period is set to 48 hours (2 day). If the queue has 75
messages after only 24 hours, these messages will print. If there
are only 15 messages in the queue at 48 hours, the 15 messages
will not print until the time period has elapsed.