Operator Interface 3-55
7000 “A” Frame
7000A-UM150F-EN-P – June 2013
Figure 3.80 – Diagnostic Setup
Figure 3.81 – Assign A Trace
From this screen, the tags to be monitored are assigned to a trace. 
The tag which you assign to the first trace 'Trace 1' is used as the 
trigger parameter. By default, when assigning a tag to Trace 1, the 
trigger value (i.e. data) will be set to the tag's minimum value and the 
trigger condition will be 'equal to'. A tag must be assigned to Trace 1 
before the trigger value or condition can be set. From this screen 
you may also set the interval between samples (i.e. Rate), and the 
location of the trigger point within the view buffer. By default, the 
trigger will occur in the middle of the buffer, however you may 
change this by indicating the percentage of samples which will 
follow (i.e. Post) the trigger point. 
Assigning a Trace
 
 
To assign a tag to a trace, use the [cursor up] and [cursor down] 
keys. Highlight the desired trace and press the [enter] key. Since 
there are more traces then can be seen on a single screen, use the 
up/down arrow keys to extend the list to the additional traces on the 
screen. (If nothing happens then you have not gained the required 
access to make changes. Press the [F8] key and refer to the section 
entitled Enter/Modify an Access Level to gain access).