Component Definition and Maintenance 6-55
7000 “A” Frame
7000A-UM150F-EN-P –June 2013
8. Now, calculate the capacitance from the measured values of test
voltage and current. For a good capacitor, the calculated capacitance
value for each of the three readings should be within +10% of the
capacitor nameplate micro-Farad. If it is outside this range then the
capacitor must be replaced.
Example: An example is given below to illustrate how the capacitance
value is calculated.
Suppose a capacitor under test is rated at 400kVAR, 6600V, 50Hz, 9.2
F.
Let us say, you are using 200V, 50Hz test power and have recorded the
values of voltage and current for each test as given in the table below.
Phase - Neutral
L1-N
L2-N
L3-N
Test Voltage
200V
200V
200V
Measured Current
1.87A
1.866A
1.861A
Let us calculate the capacitance using the first reading. In this case:
V = 200V, I = 1.87 for L1-N
Xc = V/I = 200/1.87 = 106.95
F
C
C
Xc
f
C
7
.
29
95
.
106
50
14
.
3
2
1
2
1
Where, f = frequency of the applied voltage.
Similarly, you can calculate the capacitance for the remaining two
measurements for L2-N and L3-N.