Transient suppression network fuse replacement – Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual
Page 317

Component Definition and Maintenance 6-13
7000 “A” Frame
7000A-UM150F-EN-P –June 2013
Transient Suppression Network Fuse Replacement
Two sizes of fuses (5 kV, 7.2 kV) are available within the Transient
Suppression Network (TSN) located inside the connection cabinet.
1. Ensure there is no power to the equipment.
A T T E N T I O N
A T T E N T I O N
To prevent electrical shock, ensure the main
power has been disconnected before working
on the drive. Verify that all circuits are voltage
free using a hot stick or appropriate voltage-
measuring device. Failure to do so may result
in injury or death.
2. Fuses are held in a place with a fuse clip. To remove the fuse pull
firmly.
3. To replace the fuse, hold it in position and push firmly until the fuse is
seated within the fuse clip. Install fuses so that the rating is visible,
and the rivets are not against the clips.
I M P O R T A N T
I M P O R T A N T
Make sure to replace the fuse with another of the
same rating. (See Figures 6.12 and 6.13 for
location.)
Location of ground
Varistors
Connecting Links
Location of 5 kV fuses
Varistors
Figure 6.12 –Transient Suppression Network – 2300 V and 4160 V