Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual
Page 453
 
Troubleshooting
7-15
7000 “A” Frame
7000A-UM150F-EN-P – June 2013
FAULT
MESSAGE
FAULT
CODE
DESCRIPTION
RECOMMENDED ACTIONS
Master CurrentUB
163
The measured and calculated phase 
currents in the Master Bridge have 
exceeded the value set in Line Current 
Unbalance Trip (P108) for the duration set in 
Line Current Unbalance Delay (P109). 
– Verify that all Current Transformer
connections are connected properly and 
that no wires are reversed – Ring-out 
wires to verify connections
– Check grounding on CTs 
– Ensure that all plugs are firmly 
connected in the SCBL
– Check that all input voltages are
balanced
– Verify Parameter settings 
– Check the burden resistors 
– Verify the Input Capacitor values if 
installed
– Verity that there are no open sharing
resistors.
– Verify all Line Thyristors are firing in
Gating Test Mode Check the Line Filter 
Capacitors (for PWM rectifier drives). 
Refer to Chapter 6 of the user manual for 
detailed instructions on Testing Filter 
Capacitors. 
Master VoltageUB
160
The measured phase voltages in the Master 
Bridge have exceeded the value set in Line 
Voltage Unbalance Trip (P271) for the 
duration set in Line Voltage Unbalance 
Delay (P272).
– CHECK TSN FUSING 
– Verify the VSB connections and tap 
settings, and check resistance of VSB
board – Megger board to confirm integrity
– Check actual voltage values on the
Operator Interface terminal for each 
bridge and the total line voltage 
– Check for possible source voltage supply
problems
– Use Multimeter and Oscilloscope to
check voltages on the drive voltage test
points
Motor Current UB
33
The measured current unbalance on the 
drive output has exceeded Mtr I UB Trip 
(P208) for the duration set in Mtr I UB Delay 
(P214).
– Verify the current sensor wiring and
Burden Resistors from the Motor current 
sensors 
– Verify the HCS power 
– Check the Motor Filter Capacitors for 
balanced loading on all 3 phases. Refer
to Chapter 6 of the User‟s Manual for 
detailed instructions on Testing Filter 
Capacitors 
– Investigate the possibility of Motor
winding or cabling problems