Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual
Page 481
 
Troubleshooting
7-43
7000 “A” Frame
7000A-UM150F-EN-P – June 2013
WARNING
MESSAGE
WARNING
CODE
DESCRIPTION
RECOMMENDED ACTIONS
Master UV
112
The measured value V Master Average 
(P136) is less than Line Undervoltage Trip 
(P167) with respect to 1/3 Rated Line 
Voltage (P18) [for 18-pulse drives], and 
Rated Line Voltage (P18) [for 6-pulse and 
PWM drives] for the period set by Line 
Undervoltage Delay (P168).
– Verify the VSB connections and tap
settings, and check resistance of VSB 
board – Megger board to confirm integrity 
– Check TSN fusing 
– Check actual voltage values on the 
Terminal for each bridge and the total 
line voltage 
– Check for possible source voltage
supply problems
– Use Multimeter and Oscilloscope to
check voltages on the drive test points
Motor Cap Range
23
The calculated per unit value of the Motor 
Filter Capacitor (P128), based on the values 
entered for Motor Capacitor kVAR (P20), 
Motor Capacitor Volts (P21), and Motor 
Capacitor Frequency (P28) is outside of the 
normal range of 0.26-0.55 pu. 
– Verify capacitor nameplate data and
compare with information entered in 
drive 
– Contact factory
Motor DC Link OV
192
DC Link Voltage on the motor side, 
measured through the Voltage Sensing 
Board, has exceeded Motor DC Overvoltage 
Trip (P193), and instantaneously causes a 
warning. 
– Verify the motor is connected and the
Output Contactor is not open
– Verify there is no open SGCTs Complete
a Resistance and Firing check
– Check VSB circuit (grounds) through to
SCB-M
– Check Burden resistor values 
– Check the trip parameter setting 
Motor Load Loss
41
The drive has detected a loss of load 
condition. This is activated as a warning 
using the parameter Load Loss Detect 
(P199), and the necessary setpoints are 
Load Loss Level (P246), Load Loss Delay 
(P231), and Load Loss Speed (P259).
– Verify the parameter settings 
– Ensure that the load should not normally 
be in an unloaded condition
Motor OL
17
A Motor Overload warning has been
detected, where the overload condition is 
calculated using I Stator (P340) and Motor 
Overload Warning (P351) as the point 
where the overload warning occurs. P351 is 
programmed as a percentage of the 
difference between Motor Overload Min 
(P350) and Motor Overload Trip (P179). 
– Transient Loading - Check torque limit
and overload settings and Compare
loading to torque settings and trip 
settings 
Motor OV
193
The measured Motor AC Voltage has
exceeded Motor Overvoltage Trip (P181) for 
the duration set in Motor Overvoltage Delay 
(P182), but this has occurred with the drive 
NOT gating (as in a Sync Transfer event) 
Possible Causes: 
Noise from contactor closure 
Self-Excitation – Check for flying 
start/induced motor rotation 
Motor Protection
68
Standard External Fault/Warning Input 
included to allow the end-user to install a 
protective relay (IE Bulletin 825 Motor 
Protection Relay) auxiliary contact that can 
activate a drive fault or warning, depending 
on configuration of Motor Prot Class (P443). 
– See associated Fault Description