7000 “A” Frame
The diagnostic trending is a valuable tool for troubleshooting faults in the 
drive. It is a method of capturing the variation in the values of different 
variables over a period of time prior to and after a fault or warning 
condition. In a classic drive, the maximum number of parameters that can 
be assigned for trending is 8. The length of the trend buffer is 100 samples. 
Diagnostic Setup
The diagnostic setup is used to define the source of the diagnostic trigger. 
Information that has to be programmed in the diagnostic setup is listed 
below: 
Trace
The Read-Only Parameter which is assigned to a particular 
list. The item linked to Trace 1 is used as the trigger value. 
There are 8 traces in total, although not all have to be active. 
 
Rate 
The time delay between sample periods. Any value between 0 
and 20,000 msec can be set. Use numeric keypad to enter the 
value and press the enter key to accept. 
 
Post 
The percentage of the list which will occur after the after the 
trigger point. Any value between 0 and 100% may be used. 
 
Trigger 
Defines whether you want a continuous or a single-shot 
trigger. Pressing this key will place an S or a C in front of the 
trigger parameter. You will almost always want a Single-Shot 
(S) trigger. 
 
S = Single shot >> the trigger occurs only once and stops. The 
trigger must be manually re-armed. The Re-Arm function 
clears the memory buffer, which contains the data stored from 
the previous trend. It is necessary to reset the trending feature 
in order for a second trigger to occur, unless you have 
continuous trigger enabled. 
 
C = Continuous capture >> auto re-arm is enabled to collect 
new trends until stopped by viewing contents of captured 
data. 
 
Cond
Defines the condition that will cause the trigger. The possible 
options are: 
= Equal to
+ Boolean OR
N= Not Equal to
N+ Boolean NOR
> Greater than
& Boolean AND
< Less than
N& Boolean NAND
Data
Defines the trigger value with respect to the read-only 
parameter in Trace 1. 
Setting up Diagnostic
Trending