Analog outputs – Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual
Page 303

Functional Description 5-35
7000 “A” Frame
7000A-UM150F-EN-P – June 2013
Analog Outputs
A total of thirteen programmable analog outputs are provided on
various boards. There are two analog outputs on each SCB and 1 on
the CIB, which are intended for diagnostic purposes and are available
as test points for connection to an oscilloscope or chart recorder.
These analog outputs are 8-bit, non-isolated, with a range of -10V to
+10V. The CIB has one isolated 4-20mA or 0-20mA analog output
and 7 non-isolated analog outputs for connection to external devices
such as meters or isolation modules. The allocation of the analog
outputs is shown below:
No.
Output
Board
Description
1
Rect_TP1
SCBL
DAC_TP1
2
Rect_TP2
SCBL
DAC_TP2
3
Inv_TP1
SCBM
DAC_TP1
4
Inv_TP2
SCBM
DAC_TP2
5
Cib_TP4
CIB
CIB_TP4
6
4-20mA
CIB
Connector J4b
7
CIB_Port1
CIB
Connector J5b
8
CIB_Port2
CIB
Connector J5b
9
CIB_Port3
CIB
Connector J5b
10
Meter Port 1
CIB
Connector J9
11
Meter Port 2
CIB
Connector J9
12
Meter Port 3
CIB
Connector J9
13
Meter Port 4
CIB
Connector J9
Any parameter or variable can be assigned to any analog output. The
variables are scaled by using the corresponding scaling factor.