6-112
Component Definition and Maintenance
7000A-UM150F-EN-P –June 2013
7000 “A” Frame
2. Press F8 [D_SETUP]. The display will change to „Diagnostics Setup’
screen as shown in the picture below.
3. With Trace-1 selected, press Enter key as shown in the picture
below.
4. The display will change to „Select Group‟ screen as shown in the
picture below. Now there are three ways to find the desired a
parameter, (i) search by group (select the group by pressing up or
down arrow keys and then press Enter key), (ii) search by
Alphabetical order (press F7 key to move to the letters screen from
there you can search the parameter by highlighting the first letter of
the parameter and then pressing the Enter key), (iii) by entering the
parameter linear number (press F7 and then F5 for the Code). In the
following example we will select the parameter by using a Linear
number (i.e., we will enter the Code). For this follow the steps
outlined below.