Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual
Page 326

6-22
Component Definition and Maintenance
7000A-UM150F-EN-P –June 2013
7000 “A” Frame
8. Disconnect the plug that connects the thermal sensor to the circuit
board.
9. Remove the screw that attaches the thermal sensor to the heatsink.
10. Replace with the new thermal sensor and cable assembly.
11. Note there is a small voltage difference between the thermal sensor
and its heatsink. For proper function, it is essential to mount the small
insulating pad between the thermal sensor and the heatsink and the
insulating bushing between the thermal sensor mounting screw and
the thermal sensor (see Figure 6.20).
12. Replacement of the heatsink with the new thermal sensor is in the
reverse order of removal.
13. Follow procedure “Uniform Clamping Pressure” to ensure the
heatsinks are clamped to a uniform pressure.
Insulating bushing
Mounting pad
Temperature feedfack
circuit board
Mounting screw
Thermal sensor
and cable assembly
Figure 6.20 – Replacing the Heat Sensor