Commissioning 4-19
7000 “A” Frame
7000A-UM150F-EN-P – June 2013
Control Wiring
 
 
Identify all customer-required control wiring detailed on the 
electrical diagram and located it within the terminal blocks in the 
drive. Examine it to verify that the cable insulation has not been 
tightened into the terminal. Verify that all connections have proper 
continuity. 
 
 
Ensure factory jumpers installed and marked with notes “to remove 
if remote equipment installed” have been removed. 
 
 
Inspect the control cable routing to ensure that DC Control wiring 
and AC control wiring are separated from each other. Routing them 
together in the same bundle, wire-way or panduit may result in 
unwanted noise being induced in the drive control. In the overhead 
cable tray provided at the front of the drive, ensure that the AC 
Control, DC control and Fiber optic cables remain isolated from each 
other by the dividers provided. 
 
Inspect for additional control not shown on the electrical diagram. 
Determine its purpose, mark the changes on the electrical diagram 
and send the prints to the factory for future reference. 
 
 
Perform a tug test on all control cables to ensure that they are 
securely fastened, and check each plug and connector to ensure it is 
properly seated in its socket. 
A T T E N T I O N
A T T E N T I O N
Ensure that there is sufficient clearance 
between the installed control wiring to the 
control cabinet and components carrying 
medium voltage. Verify that closing the low 
voltage door does not swing the low voltage 
cables into the medium voltage cabling section.