Rockwell Automation 7000A PowerFlex Medium Voltage Drive (A-Frame) - Classic Control User Manual
Page 484
 
7-46
Troubleshooting
7000A-UM150F-EN-P – June 2013
7000 “A” Frame
WARNING
MESSAGE
WARNING
CODE
DESCRIPTION
RECOMMENDED ACTIONS
Rec Heatsink OT
121
The temperature detection on the Rectifier 
Heatsink, connected to Channel A fiber optic 
receiver RX7 on FOI-L-A, has exceeded 
Rectifier Heatsink Temperature Warning 
(P112). 
– Confirm actual temperature in
parameters is not higher than the 
warning value – If so, investigate the 
conditions of the drive (ambient / loading 
/ elevation / ventilation/ filter status / 
heatsink clogging) 
– Check TFB and FOI board for power
and fiber optic integrity
– Check the sensor and temperature
offline (ambient) for accuracy
Rec ChannelB OT
122
Not Normally Used – The temperature 
detection on a Rectifier Heatsink, connected 
to fiber optic receiver RX7 on FOI-L-B, has 
exceeded Rectifier Temperature Warning 
Channel B (P526). 
Rec HS Sensor
201
While Running, the drive has detected a
missing temperature sensor connected to 
the TFB on the rectifier heatsink. A missing 
sensor can result in either a Fiber Optic 
Loss fault or a Sensor fault because a 
missing sensor can be interpreted as either 
0°C or over 100°C, and both are unrealistic 
values. 
– Verify sensor is completely seated
properly on TFB.
– Measure sensor resistance. 
– Replace if necessary. 
– NOTE: This is a warning because the
drive should not fault on the loss of the
signal while running. There is no 
imminent danger to the drive, but the 
user needs to be aware that there is a 
temperature feedback signal missing. 
 
Rec ChB Sensor
202
Not normally used: While Running, the 
drive has detected a missing temperature 
sensor connected to the optional TFB 
connected to the fiber optic receiver RX7 on 
FOI-L-B. A missing sensor can result in 
either a Fiber Optic Loss fault or a Sensor 
fault because a missing sensor can be 
interpreted as either 0°C or over 100°C, and 
both are unrealistic values. 
Reg in Limit
51
Either the Speed Regulator or the Flux 
Regulator autotune test hit the regulator limit 
and the results of the test are not valid.
– REFER TO THE POWERFLEX 7000
SERIES B MANUAL (CHAPTER 4 –
COMMISSIONING) ON AUTOTUNE 
PROCEDURES, RESULTS, AND 
ACTIONS 
Slip Range
189
This warning appears when unusual values 
for slip appear, indicating there is either an 
error in data or an unusual motor. The rated 
slip for this warning has to be > 10%, or < 
0.01% 
– Verify Motor Nameplate Data 
– Contact the factory with the motor data 
and the application information
Slave 0-7 OffL
348-355
Slave (0-7) DAN Communication Loss-
Master only 
– Slave is Off line.
Slave1 UV
113
The measured value V Slave1 Average 
(P137) is less than Line Undervoltage Trip 
(P167) as a percentage of 1/3 Rated Line 
Voltage (P18), for the period set by Line 
Undervoltage Delay (P168). 
– Verify the VSB connections and tap
settings, and check resistance of VSB 
board – Megger board to confirm integrity 
– Check TSN fusing 
– Check actual voltage values on the 
Terminal for each bridge and the total
line voltage
– Check for possible source voltage
supply problems
– Use Multimeter and Oscilloscope to
check voltages on the drive test points
Slave2 UV
114
The measured value V Slave2 Average 
(P138) is less than Line Undervoltage Trip 
(P167) as a percentage of 1/3 Rated Line 
Voltage (P18), for the period set by Line 
Undervoltage Delay (P168).