Commissioning
7000A-UM150F-EN-P – June 2013
7000 “A” Frame
A T T E N T I O N
A T T E N T I O N
Ensure that the motor is not spinning due to a 
driven load. A spinning motor can generate a 
high potential into the drive‟s motor filter 
capacitors, which can result in severe injury or 
death. 
 
 
Refer to local safety guidelines for detailed procedures on how to 
safely isolate the equipment from hazards. 
 
 
The door to the medium voltage cabinets can only be opened after 
the lockout/tagout are successfully completed. 
Step Down Transformer Fusing
 
 
Transformers are used in the drive to step down medium voltage to 
low voltage. With all sources of power removed from the drive 
(Medium Voltage and Control Power), remove the step down 
transformer fuses from the fuse clips and place them in a safe place 
outside of the drive cabinet. Removing the control power fuses will 
prevent a separate source of control power from being stepped up to 
Medium Voltage in the event that the safety interlocks fail to 
function. 
 
 
Fuse and O/L Protection
 
 
While referencing the electrical diagrams, locate all fuses and 
overload relays within the drive line-up. Verify that all installed 
fuses and overload are the same as indicated by Rockwell 
Automation. Fuses and overload settings are also identified by 
stickers located on the cabinet structure in proximity to the fuse or 
overload. Ensure the settings match the rating identified on the 
sticker. 
 
 
Replacement fuses have been shipped with the drive in the event that 
a fuse opens during commissioning.