Configuring preview states – Rockwell Automation 2711E-ND1 Reference Manual PanelBuilder 1400e User Manual

Page 132

Advertising
background image

126

Scrolling Lists

Publication 2711E-6.15 – November 1998

Configuring Preview States

The Number of Preview States you define for a cursor list
determines the minimum number of visible states that will appear
above or below the cursor before the list begins to scroll.

In PanelBuilder, Version 2, the maximum Number of Preview States
is calculated differently than in earlier versions. The following table
illustrates the different calculation methods:

Formula for Maximum Number of Preview
States, pre-Version 2

Formula for Maximum Number of Preview
States, Version 2

Number of Visible States/2 – 1

(Number of Visible States + 1)/2 – 1

Note: If you use a maximum number that is higher than the number
obtained using the earlier method, the application will be compatible
only with PanelView Firmware Version 2 or later. The application
will not be compatible with earlier versions.

The following table illustrates the different results produced by the
two methods:

Number of
Visible States

Maximum Number of Preview
States, pre-Version 2

Maximum Number of Preview
States, Version 2

5

5/2 – 1 = 1.5 = 1 (rounded down)

(5 + 1)/2 – 1 = 2

6

6/2 – 1 = 2

(6 + 1)/2 – 1 = 2.5 = 2 (rounded down)

The following illustration shows an example of how the preview
state option works when the Number of States is 7, the Number of
Visible States is 5, and the Number of Preview States is 1.

"

Advertising