Using the decimal point (input component) – Rockwell Automation 2711E-ND1 Reference Manual PanelBuilder 1400e User Manual

Page 84

Advertising
background image

78

Numerics

Publication 2711E-6.15 – November 1998

PLC Controlled—Select this option if you want the position of
the decimal point to be determined by the PLC. This means that
the decimal point is not in a fixed position, and the PLC controls
the number of digits after the decimal point.

If the Displayed Value control is a fractional number and has
fewer than the specified number of digits, the value is padded
with zeroes. If the value has more than the number of digits, the
value is rounded off.

If you select this option, you must define the Displayed Decimal
Point Position control.

If the PLC’s value is invalid or greater than 15, this field is filled
with asterisks (***).

Fixed Position—Select this option if you want the decimal point
to appear always in the same position. You must specify the
number of digits to appear after the decimal point. Enter a value
between 1 and 15.

Using the Decimal Point (Input Component)

The Numeric Input Cursor Point has both a display and an input
component. See “Using the Decimal Point” later in this chapter for
information about the decimal point options for the input component.

Configuring the Numeric Input Cursor Point

Configure the Numeric Input Cursor Point according to the
following tables.

Name

Field

Meaning

Name

Assign a name, up to 15 characters, to document the object for
printed reports. This increases the application’s size by 1 byte
per character.

Advertising